• US06&US12

US06&US12

型號 : US06&US12

Specifications
Range: US06: 8” to 19.6’ (20cm to 6m)
US12: 18” to 39.3’ (45.7cm to 12m)
Accuracy: ± 0.2% of range
Resolution: US06: 0.079” (2mm)
US12: 0.196” (5mm)
Dead band: US06: 8” (20.3cm)
US12: 18” (45.7cm)
Beam width: US06: 3” (7.6cm)
US12: 6” (15.2cm)
Configuration: Push button or WebCal® PC
Windows® USB® 2.0
Memory: Non-volatile
Display type: LCD, 6-digit
Display units: Inch, cm or percent
Supply voltage: 14-28 VDC
Loop resistance: 500 ohms @ 24 VDC
Signal output: 4-20mA, two-wire
Signal invert: 4-20mA or 20-4mA
Signal fail-safe: 4mA, 20mA, 21mA, 22mA, hold last
Process temp.: F: -40º to 176º
C: -40º to 80º
Temp. comp.: Automatic
Ambient temp.: F: -40º to 176º
C: -40º to 80º
Pressure: 30 psi (2 bar)
Enclosure rating: Type 4X (IP66)
Encl. material: Aluminum
Enclosure vent: Water tight membrane
Conduit entrance: 1/2” NPT
Transducer type: Reflective
Transducer mat.: Polyvinylidene fluoride
Process mount: 06-0001: 2” NPT
06-0011: 2” G
12-0001: 3” NPT
12-0011: 3” G
Mount gasket: -0001: N/a
-0011: Viton®
Classification: Intrinsically safe
Approvals (for USA): Class I, Div 1, Groups A, B, C & D T4;
Class II, Div 1 Groups E, F & G T4;
Class III T135C;
Class I, Zone 0, IIC AEx ia T4 Ga;
Class II, Zone 20, IIIC AEx ia, T135C, Da
(for Canada): Class I, Div 1, Groups A, B, C & D T4;
Class II, Div 1 Groups E, F & G T4;
Class III T135C
(for IECEx): Ex ia IIC T4 Ga;
Ex ia IIIC, T135C Da;
Tamb: -40 to 80C
Entity parameters: See control drawing #600820
Compliance: CE, RoHS

相關產品